Anti-Vandal covers are designed to fit over standard dry riser cabinets. The cover opens left to right via piano style hinge. It is locked by FB1 padlock supplied with cover. The rear of the cover allows for bolting to wall via multiple 10mm holes (Fixings not supplied). Supplied with Dry Riser Label.
The Dry Riser Inlet Cabinet and system is normally a dry unit that is charged by the fire brigade in the event of an emergency. An inlet breeching at ground level provides the connection to the water supply.
Breeching inlets have either 2 or 4 inlet connections complete with 2.5” male instantaneous inlets to BS336 fitted with non-return valves, 1” drain valve and caps and chains.
A 100mm (4”) rising main uses a 2-way inlet breeching in a vertical or horizontal position. A 150mm (6”) rising main uses a 4-Way inlet breeching. Inlet Breechings comply with the requirements of BS 5041 Part 3.
The Breechings are normally housed within inlet cabinets, floor mounted cabinets do not conform to BS 5041 Part 5 therefore separate local fire authority approval is required.
Cabinets for foam inlets are available on request.
Part Number:10905803 & 10905804 Dry Riser Anti Vandal Cover
Material:16SWG Zintec Steel
Finish: Rear Powder RAL3020